Natural gas detector / valve specifications
Detector
Alarm trigger level: Between 5% and 20% of Lower Explosive
Limit (LEL)
Stabilisation time after power applied: up to 4 minutes
Response time: within 30 seconds
Audible sounder: 85 dB at 3 m
Outputs: 2 relays (SPCO)- Relay 1 for controller - Relay 2 for
remote signalling
Operating temperature: -10°C to +40°C
Size: 110 x 110 x 57 mm (4.3 x 4.3 x 2.2 inch)
Power: 240v ac
Fuse rating: 3A
Double insulated - no earth connection required
Power consumption: 4 w quiescent
Expected Life: 5 years

Controller
Alarm reset: auto reset key switch
Operating temperature: -10°C to +40°C
Size: 150 x 90 x 65 mm (5.9 x 3.5 x 2.6 inch)
Power: 240v ac
Fuse rating: 3A
Double insulated - no earth connection required
Power failure - failsafe mode will switch off valve on mains
power failure (option, can be disabled)
|
|
Easy fit shut off valve
Installation: Fitted into gas pipe to appliance
Fitting: standard bayonet fitting
Cable length: 4 metres (for connection to controller)
Size: 140 x 115 x 45 mm (5.5 x 4.6 x 1.8 inch)
Location: Does not protrude beyond normal pipe wall fittings
Power consumption: zero quiescent
Temperature rise: 0°C quiescent
Certified to BSEN13611.2000 (Safety and control devices for gas
burners and gas burning appliances)
Certificate number EC-87/06/004
Operational life: over 100,000 operations
Disclaimer: These details
are provided for information purposes only. They cannot be used
as part of any contract.